Skip to main content

Steering Simulation controls

The Steering Simulation tab is the primary interface for interacting with the live simulation. It holds everything to do with the running model, in three columns:

  • Left: the controls described on this page: pull-wire deflection, gravity, goal seek, the proximal fixture, and Run/Pause.
  • Center: the 3D viewer, with its preset-view toolbar floating in the corner.
  • Right: the live readouts, documented on Simulation Readouts.

Drag the splitters between the columns to resize them; VirtuCath remembers where you put them.

The simulation parks itself when you leave

Leaving this tab pauses the physics and stops rendering, and the status bar reads SUSPENDED. Coming back resumes it exactly where it was, and only if it was actually running when you left, so a paused model stays paused. This is why switching to Analysis or a tool tab never costs you CPU or changes the deflection state.

Steerable Catheter Simulation: Deflection, Wire Tension and Bend Radius · recorded on VirtuCath 1.7.2 · Watch on YouTube

Catheter Motion Controls​

This section allows for the control of catheter deflection by simulating pull-wire displacement. The controls shown will automatically adapt based on the catheter's pull-wire configuration (e.g., the Y-axis control is only enabled for four-pull-wire designs).

  • Jog Control (X & Y): This control incrementally adjusts pull-wire displacement.

    Clicking a button jogs the position in the indicated direction (+X, -X, +Y, or -Y). Each of the three rings corresponds to a different step size, allowing for fine, medium, or coarse adjustments. Clicking the Home button resets that axis to its zero position.

  • Deflection Input Box Located below the dials, this field serves two functions:

    • Readout: It displays the current commanded displacement for the axis.
    • Direct Input: A precise numerical value for deflection can be typed directly into the box.

A single pull wire set on the center line bends the catheter toward +X, as a single off-center wire does. The simulation places it 0.01 mm off the axis. A wire exactly on the axis would only compress the shaft, so nothing would bend.

When pull wires are set on the center line of a Manual Stiffness section, they run loose inside the bore: each pulled wire moves to the inside wall of each bend as the catheter bends, so it pulls with the full bore clearance as its lever arm once the section has started to bend. With two or four wires, pulling a wire bends the catheter toward that wire's side.

Additional Controls​

  • Gravity: Toggle gravity inside the simulation on and off and set the gravity vector direction.
  • Pull-wire friction: Off by default. Adds friction between each pull wire and its lumen: the handle force rises, the tip lags the proximal bend, and pulling and releasing differ. Set the Coefficient (μ); 0.05 is steel wire on a PTFE liner.
  • Pull-wire stretch: On by default. The pull wire stretches under tension, so part of the handle travel goes into the wire instead of the bend. Uncheck for a wire that does not stretch.
  • Axial compression: On by default. The shaft shortens under the pull-wire load, so part of the handle travel goes into compression instead of the bend. Uncheck for a shaft that does not shorten.
  • Goal Seek: Use one of the quick set buttons or enter an angle and VirtuCath™ will adjust the pull-wire displacement to achieve the target angle.

Pull-wire friction, pull-wire stretch and axial compression take effect immediately, with no rebuild.

Wire friction in a compression coil​

When the pull wires run in a compression coil and Pull-wire friction is on, the wire also rubs on the coil wherever the shaft behind the coil stop is bent. The tension that reaches the coil stop is the handle tension times exp(-μ x θ), with μ the same Coefficient and θ the total bend angle of the coil path; releasing, it is times exp(+μ x θ). For example, μ = 0.1 over a 90° bend passes 85% of the handle tension on the pull and 117% on the release. A straight shaft has no coil friction. The coil carries the friction force, so the shaft behind the stop still takes no wire load. The friction readouts show the coil's bend angle and the tension at the coil stop. Simulated, not measured.

Proximal Shaft Fixture​

  • Constrain proximal shaft: Emulates a bench fixture or anatomy (such as a hemostasis valve) that rigidly holds the shaft straight along its proximal length, so only the free distal length deflects. A yellow ring is drawn on the shaft in the 3D Viewer to mark the fixture point: everything proximal of the ring (toward the base) is held straight, and everything distal of it keeps deflecting under pull-wire tension. This is enabled by default at 150 mm from the tip.

    Set the distance from the tip to slide the ring. It moves live, with no model rebuild, so you can reposition the fixture while the simulation runs. Uncheck Constrain proximal shaft to let the entire shaft deflect freely. Catheters shorter than the set distance are unaffected: the ring sits at the base and no joints are locked.

Simulation Controls​

  • Run/Pause Simulation: This is a toggle button that controls the physics engine. When the simulation is paused, the button text is "Run Simulation". When active, the text changes to "Pause Simulation".
  • Reset: Stops the simulation, resets the catheter to its initial straight configuration, and clears all data.

Why simulations pause after 30 minutes: The physics engine keeps accumulating state as long as it's running, even when the catheter is idle and nothing is changing on screen. Pausing automatically at the 30-minute mark caps that memory growth on long-running sessions. Click Run Simulation to resume; the loaded model and current deflection state are preserved, so the simulation picks up exactly where it left off.

  • Catheter Setup Tab: define the design that you'll drive here.
  • Simulation Readouts: the runtime metrics in this tab's right-hand column.
  • 3D Viewer: visual companion for the live simulation.
  • Model Accuracy: accuracy of the underlying steering-simulator physics, with downloadable verification reports.